Beacon 200
Two Channel Wall Mount Controller
 The Beaconª 200 is a powerful, low cost fixed system controller for
two points of gas detection. It is microprocessor controlled, versatile,
simple to install and operate, and priced to be the industry's most
economical two point controller. It is capable of connecting directly to
RKI sensors for LEL level combustibles, Oxygen, Hydrogen Sulfide, or
Carbon Monoxide. The Beaconª 200 can also accept any 4-20 mA transmitter
(2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beaconª
200 housing, or can be wired remotely from the controller.
The 10 amp rated relays are strong enough to actuate most
external alarms and horns without using slave relays. The digital
display has backlighting and simultaneous readout of the gas type and
concentration.
The Beaconª 200's housing is rated NEMA 4X for corrosion
resistance and a weather tight seal, and complies with lock out / tag
out standards. An external reset switch allows the alarm to be silenced
from outside of the controller housing. The Beaconª 200 comes complete
with a wall mounting kit for easy installation.
RKI offers the industry's widest selection of standard
and toxic gas detection sensors, which can be utilized with the Beaconª
200, providing gas monitoring protection for almost any application.
Features
- Simultaneous readout on 2 channels
- Two alarm levels per channel
- Discrete and common relays
- NEMA 4X enclosure
- 4-20 mA outputs
- Proven, long-life sensors for a wide variety of gases
- Accepts any 4-20 mA transmitter input (24 VDC)
- Easy to install, operate and expand
Applications
- Petrochemical plants
- Refineries
- Water & wastewater treatment plants
- Pulp & paper mills
- Gas, telephone, & electric utilities
- Parking garages
- Manufacturing facilities
- Steel
- Automotive
- HVAC
Specifications
Physical |
|
| Dimensions |
Height: 10.5” 267 mm Width: 8.5” 216 mm Depth: 6.3” 158 mm |
| Enclosure |
Wall mounting grey polycarbonate with hinged cover |
Conduit
Connection
|
3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power & relay wiring |
Wiring
Termination
|
Screw type terminal block, 14 gauge max |
|
Controls |
4 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset |
|
|
Environmental |
|
| Operating Temp |
-4°F to 122°F (-10°C to 50°C) |
| Storage Temp |
-4°F to 158°F (-20°C to 70°C) |
Relative
Humidity |
0 - 100% RH |
Enclosure
Rating |
NEMA-4X enclosure, waterproof, chemical, and weather resistant |
|
|
Inputs |
|
| Direct Wired Sensors |
LEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide
Remote amp not required for less than 500 feet |
| 4-20 mA Sensors |
Accepts any 4-20 mA transmitter (24
VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available
with 4-20 mA signals. (See list of detectable gases.) Wiring distances
up to 5000 feet |
| Sampling Methods |
Diffusion and sample draw heads available |
|
|
Outputs |
|
| Relays |
7 relays - 10 amp rating (at 115
VAC), SPDT isolated contacts. 2 relays for gas alarm levels per channel,
plus 2 relays for common gas alarm and 1 common relay for malfunction.
Relays fully programmable for: increasing or decreasing alarm, latching
or self reset, normally energized or normally de-energized, time delay
for alarm on and alarm off |
| 4-20 mA |
Signal output, 4-20 mA (into 1000 ohms impedance maximum), per channel |
| 24 VDC |
24 VDC (350 mA max) output provided to operate sample drawing adapters or other accessories |
| Display |
Alphanumeric display with backlighting. 20 characters per line; 4 lines each |
| Audible |
Built-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = fail |
| Visual |
4 LED’s on the front cover for alarm status indication, pilot, and malfunction |
Optional
Expansion Cards
|
Individual 4-20 mA (or 1 - 5 VDC) outputs
Heavy duty relay card (4 each @ 30 amps) |
|
|
Power |
115 VAC or 24 VDC standard, Optional 230 VAC. Battery backup option available |
|
|
Warranty |
One year materials and workmanship |
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed. |
|
Ammonia (NH3) |
0 - 75.0 ppm |
| Arsine (AsH3 ) |
0 - 0.20 ppm |
| Boron Trichloride (BCl3) |
0 - 15.0 ppm |
| Carbon Dioxide (CO2) |
0 - 1.0 % |
| Carbon Monoxide (CO) |
0 - 300 ppm |
| Chlorine (Cl2) |
0 - 3.0 ppm |
| Chlorine Dioxide (ClO2) |
0 - 1.00 ppm |
| Chlorine Trifluoride (ClF3) |
0 - 1.00 ppm |
| Combustibles |
0 -100% LEL |
| Diborane (B2H6) |
0 - 30.0 ppm |
| Fluorine (F2) |
0 - 6.0 ppm |
| Hydrogen (H2) |
0 - 2000 ppm |
| Hydrogen Chloride (HCl) |
0 - 15.0 ppm |
| Hydrogen Fluoride (HF) |
0 - 9.0 ppm |
| Hydrogen Sulfide (H2S) |
0 -100.0 ppm |
| Nitric Oxide (NO) |
0 -100.0 ppm |
| Nitrogen Dioxide (NO2) |
0 - 15.0 ppm |
| Nitrogen Trifluoride (NF3) |
0 - 30.0 ppm |
| Oxygen (O2) |
0 - 25.0 % |
| Ozone (O3) |
0 - 1.0 ppm |
| Phosphine (PH3) |
0 - 1.0 ppm |
| Silane (SiH4) |
0 - 15.0 ppm |
| Sulfur Dioxide (SO2) |
0 - 30.0 ppm |
| TEOS (Si(OC2H5)4) |
0 -15/30 ppm |
|
|
|
|
D-2-4, Setia Walk, Pusat Bandar Puchong,
47160 Puchong, Selangor,
Malaysia
Tel: + 6012-921 3877; 603-5879 7121
Fax: +018 635 1593
Email: ancor.my@gmail.com
sales@gasmonitors.com.my |
|
|
|
|
|